1 Scope
      
1.1 These requirements cover the shielded and nonshielded medium-voltage power cables that are described in   (single-conductor) and   (multiple-conductor).  Multiple-conductor cables may include one or more individually jacketed non-conductive optical-fiber members.  These electrical and hybrid electrical and optical-fiber cables are for use (optical and electrical functions associated in the case of a hybrid cable) in accordance with Article 328 and other applicable parts of the National Electrical Code (NEC), NFPA 70.
        
1.2 These cables have one or more stranded copper or aluminum conductors that are insulated with a solid, extruded dielectric.  Cables that have a metal sheath or interlocked armor incorporate an effective grounding path.  A grounding conductor is optional in other cables.  Cables for direct burial are so marked and have an overall covering (see 4 for direct-burial cables that are not covered).  Cables that are for use in cable trays generally are so marked (see 1 and 2).  Cables that are sunlight-resistant generally are so marked (see 1 – 3).  Cables that are marked “MV-90”  or “MV-90 dry” have a maximum operating temperature of 90°C (194°F).  Cables that are marked “MV-105” have a maximum operating temperature of 105°C (221°F) for use where design conditions require a maximum conductor temperature above 90°C (194°F).  Cables that are marked “dry” have insulation for use only in dry locations.  All other cables have insulation that is for use in both wet and dry locations. Multiple-conductor cables that include one or more optical-fiber members are surface marked to so indicate.  Cables that are marked “oil resistant II” are for exposure to mineral oil at temperatures not in excess of 75°C (167°F).  Cables that are marked “oil resistant I” are for exposure to mineral oil at temperatures not in excess of 60°C (140°F).
        
1.3 A multiple-conductor Type MV cable that has a smooth (other than lead) or corrugated metal sheath or that has interlocked metal armor may be marked for use also as Type MC cable.
        
1.4 This standard does not include requirements for cables with concentric neutral conductors. However, it is possible to have a single-conductor cable with a concentric neutral conductor manufactured in accordance with the requirements of other standards, that meets the requirements for jacketed single-conductor shielded cable in this standard.
        
Table 1.1    Single-conductor Type MV cables          
                                                              
          
            
Voltage rating
                                
Size
                                
Use
                                
Insulation material
                                
Percent insulation level
                                
Insulation thicknesses
                                
Shield
                                
Overall covering
                                      
          
                      
8 AWG – 1000 kcmil
                                
90°C (194°F) dry
                                
XLPE or EPCV
                                
–
                                
Column A 
                                
nonshielded
                                
None
                                    
            
2400
                                
90°C (194°F) dry
                                
XLPE, EPCV, DREP, or EP
                                
–
                                
Column B 
                                
nonshielded
                                
Nonconductive jacket Column B 
                                    
                      
90°C (194°F) wet or dry
                                
XLPE, DREP, or EP
                                
–
                                
Column C 
                                
nonshielded
                                
Nonconductive jacket Column C 
                                    
            
5000
                                
8 AWG – 2000 kcmil
                                
90°C (194°F)
            or
            105°C (221°F)
            wet or dry
                                
XLPE, DREP, or EP
                                
100 or 133
                                
 or 
                                
Shielded
                                
a
                                    
            
8000
                                
6 AWG – 2000 kcmil
                                
90°C (194°F)
            or
            105°C (221°F)
            wet or dry
                                
XLPE, DREP, or EP
                                
100, 133, or 173
                                
 or 
                                
Shielded
                                
a
                                    
            
    15000
                                
2 AWG – 2000 kcmil
                                
90°C (194°F)
            or
            105°C (221°F)
            wet or dry
                                
XLPE, DREP, or EP
                                
100, 133, or 173
                                
 or 
                                
Shielded
                                
a
                                    
            
25000
                                
1 AWG – 2000 kcmil
                                
90°C (194°F)
            or
            105°C (221°F)
            wet or dry
                                
XLPE, DREP, or EP
                                
 100, 133, or 173
                                
 or 
                                
Shielded
                                
a
                                    
            
28000
                                
1 AWG – 2000 kcmil
                                
90°C (194°F)
            or
            105°C (221°F)
            wet or dry
                                
XLPE, DREP, or EP
                                
100, 133, or 173
                                
 or 
                                
Shielded
                                
a 
                                    
            
35000
                                
1/0 AWG – 2000 kcmil
                                
90°C (194°F)
            or
            105°C (221°F)
            wet or dry
                                
XLPE, DREP, or EP
                                
100, 133, or 173
                                
 or 
                                
Shielded
                                
a
                                    
            
              a  The overall covering consists of one of the following (see  for complete descriptions):
                                    
                      
1)   Conductive nonmetallic insulation covering () as part of shielding, with or without nonmagnetic metal sheath or armor over conductive nonmetallic insulation covering as part of shielding, with or without supplementary non-conductive jacket () over metal sheath or armor.
                                    
                      
2)   Non-conductive jacket () over shielding, with or without nonmagnetic metal sheath or armor over non-conductive jacket, with or without supplementary non-conductive jacket () over metal sheath or armor.
                                    
                      
3)  Nonmagnetic metal sheath or armor as part of shielding, with or without supplementary non-conductive jacket () over metal sheath or armor.
                                    
Table 1.2    Multiple-conductor Type MV cables          
                                                                    
          
            
Voltage rating
                                
Circuit conductors
                                
Grounding conductor
                                
Overall covering
                                    
            
Size
                                
Use
                                
Insulation material
                                
Percent insulation level
                                
Insulation thicknesses
                                
Shield
                                
Individual covering
                                      
          
            
 2400
                                
8 AWG – 1000 kcmil
                                
90°C
            (194°F) dry
                                
XLPE or EPCV
                                
–
                                
Column A 
                                
nonshielded
                                
None
                                
Optional Covered 1
                                
None – assembly of single-conductor cables
                                    
                                
90°C
            (194°F) dry
                                
XLPE, EPCV, DREP, or EP
                                
–
                                
Column B 
                                
nonshielded
                                
Non-conductive jacket Column B 
                                
Optional Covered 1
                                
None – assembly of single-conductor cables
                                    
                                
90°C
            (194°F) wet or dry
                                
XLPE, DREP,  or  EP
                                
–
                                
Column C 
                                
nonshielded
                                
Non-conductive jacket Column C 
                                
Optional Covered 
                                
None – assembly of single-conductor cables
                                    
                      
                                
90°C
            (194°F) or 105°C
            (221°F) wet or dry
                                
XLPE, DREP, or EP
                                
                                
Column C 
                                
nonshielded
                                
None or Non-conductive jacket ()
                                
Optional Bare 5
                                
Non-conductive jacket ()
                                    
                                                    
–
                                                              
Required Bare 1
                                
Interlocked armor with or without Supplementary jacket
                                    
                      
                                                                                            
May be required Bare 3  and 4
                                
Metal sheath with or without Supplementary jacket
                                    
            
5000
                                            
8 AWG – 2000 kcmil 
                                
 90°C
            (194°F) or 105°C
            (221°F)
                                
XLPE, DREP, or EP
                                
100
                                
, 
                                
 Shielded
                                
Non-conductive jacket () over shield
                                
Optional Covered 1
                                
None
                                    
                                                                        
Conductive nonmetallic insulation covering () as part of shield
                                
Optional Covered 
                                
None
                                    
            
                                                                                  
Metal sheath  as part of shield with  or without Supplementary jacket
                                
Optional Covered 1
                                
None
                                    
            
8000
                                
6 AWG – 2000 kcmil
                                
90°C
            (194°F) or 105°C
            (221°F) wet or dry
                                
XLPE, DREP, or EP
                                
100, 133, or 173
                                
, 
                                
Shielded
                                
None or Non-conductive jacket ()
                                
Optional Bare 5
                                
Non-conductive jacket ()
                                    
                                                                                  
Required Bare 1
                                
Interlocked armor with or without Supplementary jacket
                                    
            
15000
                                
2 AWG – 2000 kcmil
                                
90°C
            (194°F) or 105°C
            (221°F) wet or dry
                                
XLPE, DREP, or EP
                                
100, 133, or 173
                                                              
May be required to Bare 3  and 4
                                
Metal sheath with or without Supplementary jacket
                                    
                                                    
                                
                                
Non-conductive jacket () over shield
                                
Optional Covered 1
                                
None
                                    
            
25000
                                
1 AWG – 2000 kcmil
                                
90°C
            (194°F) or 105°C
            (221°F) wet or dry
                                
XLPE, DREP, or  EP
                                
100, 133, or 173
                                                    
Conductive nonmetallic insulation covering ()    as part of shield
                                
Optional Covered 1
                                
None
                                    
                                                                        
Metal sheath as part of shield with or without supplementary jacket
                                
Optional Covered 1
                                
None
                                    
            
28000
                                
1 AWG – 2000 kcmil
                                
90°C
            (194°F) or 105°C
            (221°F) wet or dry
                                
XLPE, DREP, or EP
                                
100, 133, or 173
                                
, 
                                          
None  or Non-conductive jacket ()
                                
Optional Bare 5
                                
Non-conductive jacket ()
                                    
                                                                                  
Required Bare 2
                                
Interlocked armor with or without Supplementary jacket
                                    
                                                                                  
May be required Bare 3  and 4
                                
Metal sheath with or without Supplementary jacket
                                    
            
35000
                                
1/0 AWG – 2000 kcmil
                                
90°C
            (194°F) or 105°C
            (221°F) wet or dry
                                
XLPE, DREP, or EP
                                
100, 133, or 173
                                
, 
                                
Shielded
                                
Non-conductive jacket () over shield
                                
Optional Covered 
                                
None
                                    
                                                                        
Conductive nonmetallic insulation covering () as part of shield
                                
Optional Covered 1
                                
None
                                    
                                                                        
Metal sheath as part of shield with or without Supplementary jacket
                                
Optional Covered 1
                                
None