UL CSDS Proposal
Published Date: January 23, 2015
Last Revision: June 25, 2020
Scope
006180-000000-0000001 Scope
1.1 These requirements cover concrete masonry units classified for use in fire resistive walls in accordance with the conditions of acceptance of the Standard for Fire Tests of Building Construction and Materials, UL 263.
1.2 Concrete masonry units are classified as follows:
a) 2-hour units are intended for use in fire resistive walls having a rating of 2 hours or less.
b) 3-hour units are intended for use in fire resistive walls having a rating of 3 hours or less.
c) 4-hour units are intended for use in fire resistive walls having a rating of 4 hours or less.
1.3 A product that contains features, characteristics, components, materials, or systems new or different from those covered by the requirements in this standard, and that involves a risk of fire, electric shock, or injury to persons shall be evaluated using the appropriate additional component and end-product requirements to determine that the level of safety as originally anticipated by the intent of this Standard is maintained. A product whose features, characteristics, components, materials, or systems conflict with specific requirements or provisions of this standard shall not be judged to comply with this standard. Where appropriate, revision of requirements shall be proposed and adopted in conformance with the methods employed for development, revision, and implementation of this standard.
Summary of Topics b0618_9_20150123_sum.htmlSubject 618
Bulletin Dated: January 23, 2015
SUMMARY OF TOPICS
The following is being proposed:
1. Reaffirmation and Continuance of the Ninth Edition of the Standard for Concrete Masonry Units, UL 618, as an American National Standard
Back to Standard 618, Edition 9