UL CSDS Proposal
Published Date: March 24, 2017
Last Revision: July 03, 2018
Scope
002600-000000-0000001 Scope
1.1 These requirements cover valve equipment intended for installation in piping systems to supply water automatically to dry pipe, deluge, and pre-action sprinkler systems for fire-protection service.
1.2 Valves covered by these requirements may be a differential type, latched-clapper type, or a combination of these types.
1.3 The valves covered by these requirements are intended for installation and use in accordance with the following standards:
a) Standard for Low-, Medium-, and High-Expansion Foam, NFPA 11.
b) Standard for the Installation of Sprinkler Systems, NFPA 13.
c) Standard for the Installation of Standpipe and Hose Systems, NFPA 14.
d) Standard for Water Spray Fixed Systems for Fire Protection, NFPA 15
e) Standard for the Installation of Foam-Water Sprinkler and Foam-Water Spray Systems, NFPA 16
1.4 This standard does not cover low-differential dry pipe valves or valves with differentials outside of the requirement specified for differential dry pipe valves.
Summary of Topics b0260_7_20170324_sum.htmlSubject 260
Bulletin Dated: March 24, 2017
SUMMARY OF TOPICS
The following is being proposed:
1. Reaffirmation and Continuance of the Seventh Edition of the Standard for Safety for Dry Pipe and Deluge Valves for Fire-Protection Service, UL 260, as an American National Standard
Back to Standard 260, Edition 7