UL CSDS Proposal
Published Date: January 05, 2018
Last Revision: March 17, 2021
Scope
000040-000000-0000001 Scope
1.1 These requirements cover interlocked steel or aluminum armored cables that contain 2, 3, or 4, 14 – 1 AWG insulated circuit conductors with or without grounding conductors and are for use as Type AC Armored Cable in accordance with Article 320 and other applicable parts of the National Electrical Code (NEC), ANSI/NFPA 70.
1.2 These requirements cover cables for use at potentials of 600 V or less and at temperatures that are not higher than 75°C (167°F) for Type ACTH, or 90°C (194°F) for Types ACHH and ACTHH, depending upon the temperature rating of the insulated conductors used. Cables with aluminum armor are suitable only for use with connectors other than the direct-bearing set-screw type and only in alternating-current circuits.
Summary of Topics b0004_15_20180105_sum.htmlSubject 4
Bulletin Dated: January 5, 2018
SUMMARY OF TOPICS
The following is being proposed:
1. Reaffirmation and Continuance of the Fifteenth Edition of the Standard for Armored Cable, UL 4, as an American National Standard
Back to Standard 4, Edition 15