UL CSDS Proposal
Published Date: July 13, 2018
Last Revision: November 07, 2023
Scope
007190-000000-0000001 Scope
1.1 These requirements cover nonmetallic-sheathed cables containing 2 – 4 thermoplastic-insulated circuit conductors, with a grounding conductor, in the constructions indicated in . These cables are intended for use in accordance with Article 334 and other applicable parts of the National Electrical Code, NFPA 70. Type NMC cable is for use in dry, moist, damp, and corrosive locations, and Type NM cable is for use in normally dry locations. Both types carry the suffix letter "-B" to designate the use of conductors with 90°C insulation.
1.2 A cable to which the designation "ST1" (signifying "limited smoke") is applied as a type-letter suffix complies with the test criteria for smoke release and for cable damage height stated in the Standard for Vertical-Tray Fire-Propagation and Smoke-Release Test for Electrical and Optical-Fiber Cables, UL 1685.
Summary of Topics b0719_13_20180713_sum.htmlSubject 719
Bulletin Dated: July 13, 2018
SUMMARY OF TOPICS
The following changes in requirements to the Standard for Nonmetallic-Sheathed Cable, UL 719, are being proposed:
1. Addition of Signal/Control Conductors Used Within a Type NM Cable
Back to Standard 719, Edition 13