Scope
1.1 These requirements cover Power Control Systems (PCS) supplied by one or more power sources which may include the utility grid. PCS can be utilized to control sources, loads, or combinations of both. The PCS electronically limits or controls current or power to stay within defined limits and may consist of a single device or multiple devices operating together as a system. The current or power measurement reference point(s) may be located within the PCS equipment or elsewhere within the premises wiring system. All elements of the PCS are intended to be installed in accordance with the NFPA 70®, National Electrical Code® (NEC®) or for products intended to be installed in Canada, the Canadian Electrical Code, Part I Safety Standard for Electrical Installations, CSA C22.1.
NFPA 70®, National Electrical Code®, and NEC® are registered trademarks of the National Fire Protection Association, Quincy, MA.
1.2 PCS may be evaluated and rated for one or more of the primary types of PCS addressed in – as well as provide one or more of the PCS functions in accordance with of this Standard. See for details regarding rating requirement specifics.
1.3 A PCS may be evaluated as a single source PCS. Single source PCS provide an overload functionality when used with a passive protective device [e.g. Overcurrent Protective Device (OCPD)] used for the protection of service, feeder, or branch circuits. A single source PCS limits power consumed by loads from a single source of supply [e.g. the area Electric Power System (EPS)] via load management.
NOTE 1: Additional sources not controlled by the PCS and complying with the requirements of NEC 705.12 may be connected to a single source PCS. A single source PCS provides overload control for power or current consumed by loads from a single source of supply (e.g. from the area EPS / primary power source).
NOTE 2: A single source PCS is located in a circuit(s) where branch circuit rated OCPD’s located internal or external to the PCS provide additional protection from overloads.
1.4 A PCS may be evaluated as a multisource PCS. Multisource PCS provide critical overload functionality addressing system overload conditions of premises wiring systems (e.g. service panelboards, distribution panelboards, OCPDs and/or circuit wiring) supplied by more than one source. Multisource PCS include one or more PCS controlled source(s) and may also include load management functionality.
NOTE: A multisource PCS does not replace or eliminate the need for premises circuits to be protected by an appropriately sized OCPD per the ampacity rating of the circuit. The multisource PCS only regulates specific sources and/or loads to set levels when the combination of sources could exceed the circuit ampacity rating without the PCS control. Without the PCS control, the sources may cause an overload condition on circuits that OCPDs may not be able to protect against. Multisource PCS functionality addresses system overload conditions of the PCS controlled conductors in accordance with NEC 705.13.
1.5 A PCS may be evaluated for power import limiting (PIL) and/or power export limiting (PEL) functionality where the PCS control and monitoring point is at an external reference point of applicability, such as the point of common coupling with the area EPS. The PCS may limit current and/or power flow from generation sources to the Area EPS (exporting) or limit current and power flow from the Area EPS to loads / the local EPS (importing). PEL and PIL functions do not address overload mitigation in accordance with , items (b) – (e) (overload conditions as defined in the NFPA 70®, National Electrical Code® (NEC®) or for installations in Canada in the Canadian Electrical Code, C22.1).
NOTE: PIL / PEL functions only address utility facing functionality (area EPS side of the PCC) and do not address NEC overload conditions (local EPS side of the PCC). PCS may be evaluated only for PIL/PEL functionality, NEC overload functionality, or a combination of both functionalities. The ratings of the PCS reflect which functionalities are included in the scope of the evaluation of the PCS.
1.6 In addition to the required autonomous operation, the PCS is permitted to respond to external commands or schedules unless otherwise restricted within this standard. The format for scheduling of export or import to or from utilities is defined in this Standard, but specific communication protocols, or other methods, used for transmitting commands or schedules are outside the scope of this Standard. See Annex for further details.
1.7 The requirements in this Standard are intended to evaluate PCS that electronically control power or current flow within local EPS power distribution equipment, or import or exported to the area EPS, via use of external measurement and control devices. Such systems may be made up of generation devices (inverters, engine generators, etc.), energy storage systems, loads, load control applications (charging power/load management, etc.), circuit controllers, or other equipment used to manage the current or power flow at the point of reference. The power control function may utilize communication-based approaches and may include onsite monitoring devices and or controllers remote from the point of control.
1.8 The PCS may include multiple external reference points used to control power or current on multiple conductors or bus bars. For example, an external point of reference may be at the Point of Common Coupling (PCC) to control power flows to or from the utility grid as well as providing overload protection of the busbars in the main service panel. External reference points may also be located to control currents within a piece of equipment or on other circuits on the premises wiring.
1.9 Products and systems covered by this Standard are intended to be installed in accordance with the NFPA 70®, National Electrical Code® (NEC®) and the Canadian Electrical Code, Part I Safety Standard for Electrical Installations, CSA C22.1.
1.10 This Standard does not cover overcurrent protective devices. Overcurrent devices shall comply with UL 489 or CSA C22.2 No. 5.